beautypg.com

End of life - not recommended for new designs, A/r megapac “quick install” instructions, Mounting the autoranging megapac – Vicor Autoranging MegaPAC AC-DC Switcher User Manual

Page 10: Maximum torque is 10 lb-in, Place ring lug over output stud

background image

UG:106

vicorpower.com

Applications Engineering: 800 927.9474

Page 10

A/R MegaPAC “Quick Install” Instructions

(For Mechanical Drawing, see page 13)

Mounting the Autoranging MegaPAC

n

The Autoranging MegaPAC can be mounted on any of four sides.

n

Use #8-32 or 4mm mounting screws.

Maximum penetration should not exceed 0.15" (3,8mm).

n

Maintain 2" (5,1cm) clearance at either end for airflow.

n

Maximum allowable torque is 20 lb-in.

Input Connections

Input Power J9

n

Input AC power is applied to terminal block J9 using a pressure screw terminal.

n

Maximum torque is 10 lb-in.

n

A fuse or circuit breaker in the input line is required for safety reasons.

n

Use a maximum wire size of 10 AWG with soldered terminals.

n

The connector manufacturer recommends the wires not be tinned.

A ferrule (Phoenix P/N 32-00-58-0, purchased from other sources) can
be used to prevent fraying.

Output Connections

Power Connections

Installing ring lugs and/or bus bars on output studs:

n

The upper stud is Positive and the lower stud is the Return.

n

Remove outer nut. Do not remove or loosen inner nut.

n

Place ring lug over output stud.

n

Replace and tighten outer nut to a maximum torque of 45 lb-in.

Do Not Over-Tighten Nuts.

n

Verify all output nuts are properly installed before turning on supply.

Installing power connectors on DualPACs (J1A and J1B):

n

Use Molex mating receptacle #39-01-2060 with #39-00-0039

terminals provided.

n

Pins 1 and 4 are Positive, while pins 2 and 5 are the Return.

n

Attach terminals to 18-24 AWG stranded wire using Molex tool #11-01-0197.

FROM 47 TO 500 Hz

L1/N

RANGING

200-240 VAC

100-120 VAC

L2

HERE.

GROUND

EARTH

RUN W/O

DO NOT

MAX TORQUE ON SET SCREWS - 10 IN LBS

AUTO-

AC INPUTS

OPERATING

AC SOURCE

SINGLE PHASE

TED TO ANY

BE CONNEC-

SUPPLY CAN

THIS POWER

NOTE

J2-PIN1

J3-PIN1

0UTPUT ADJUST

+ V0UT

- VOUT

MODUPAC

6 -REMOTE SENSE

3 +REMOTE SENSE

2 & 5 -V OUT

1 & 4 +V OUT

PIN

J1B

+

4

6

-

5

+

+RS -

-RS

3

2

1

J1A

3

2

1

4

6

+RS

-RS

+

+

-

5

-

Input Panel Connectors

Single Output ModuPAC

DualPAC Output Connector

End of Life - Not Recommended for New Designs