Interface Connections (Cont.)
AC OK / Power Fail (J10-11)
This is an active high TTL compatible signal and provides a status indication of the AC
input power (see Figure 6 and Connector Pin Identification on Page 12). It is capable
of sourcing 0.5 mA at >3.2 V and sink 16 mA at <0.5 V. This signal switches to a TTL “1”
when the high voltage bus exceeds low-line condition during turn-on, and switches to
a TTL “0” 3 ms (minimum) before loss of output regulation due to the loss of input AC
power. This signal can be used to warn external control circuits of an impending loss of
power.
Auxiliary Vcc +5V/0.3A (J10-9)
The Vcc on J10-9 is an auxiliary 5V regulated power source (see Figure 7 and Connector
Pin Identification on Page 12). It is +5 Vdc +/–5% with respect to Signal Ground and can
supply 300 mA maximum. It is short-circuit-proof, but if shorted all outputs will shut
down through the Enable/Disable circuitry. The Auxiliary Vcc typically powers user
circuitry or is used with the Power Good circuitry to provide a pull-up reference for the
outputs of the DC Power Good circuit on a ConverterPAC. If used for this purpose, the
Signal Ground on J10-10 must also be connected to the J3-1 Signal Ground pin of the
ConverterPAC.
Figure 6.
AC OK / Power Fail
10K
Signal Ground
AC Power OK
11
+5V
10
J10
2.49K
PN2222
Figure 7.
Auxiliary Vcc
78M05
Auxiliary Vcc
9
0.1 µF
Signal Ground
J10
10
+5V/300 mA