beautypg.com

Return air filters, Coil, Belt and pulley – Titus VAB IOM User Manual

Page 7: Motor, Blower, Abbreviations, Operation and maintenance, Vab installation manual

background image

VAB Installation Manual

IOM-VAB-00

06-30-04

7 of 7

Operation and Maintenance

Read and observe the following statements before

operation or maintenance.

DANGER

DISCONNECT ELECTRICAL POWER TO ALL

CIRCUITS BEFORE SERVICING UNIT.

FAILURE TO DO SO MAY RESULT IN PERSONAL

INJURY FROM ELECTRICAL SHOCK OR MOVING

PARTS.

Return Air Filters

Inspect return air filters on a regular basis (at least

monthly). Clean or replace filter(s). Filter can be accessed

from either side of unit.

Caution: Never operate unit without a filter or with

filter access door removed. Damage to blower

motor may result.

Coil

The coil is easily cleaned when dry. To check or clean,

remove blower access panel, filter access door and

filter(s). Use accepted industry methods for cleaning.

Remove all foreign matter from pan and condensate drain

line. Check for rust and holes.

Belt and Pulley

Proper pulley alignment and belt tension must be

maintained at all times.
Reduce speed by adjusting pulley faces so the faces are

further apart.
Increase speed by moving the faces closer together.
Check pulley setscrews and bolts.

Motor

Proper lubrication is essential to long motor life. Use

electric motor oil or SAE20 non-detergent oil. Tighten

motor mount bracket and base bolts.

Note: Avoid over-oiling the motor. If a motor is over-

oiled, the oil may run down the motor shaft and

splatter.

Blower

Periodically check bearing for wear. Replace as required.
Check wheel for dirt accumulation and clean as required.

Abbreviations

The following table lists the abbreviations found within this

document.

Abbrev. Term

ANSI

American National Standard Institute

ASHRAE

American Society of Heating

Refrigeration Air-Conditioning

Engineers

ASTM

American Society for Testing and

Materials

CFM

cubic feet per minute

CW

chilled water

ETL

Environmental Testing Laboratory

fpi

fins per inch

fpm

feet per minute

HW

hot water

IAQ

Indoor Air Quality

J-Box

Junction Box

lbs

pounds

NEC

National Electric Code

OD

outside diameter

ODP

open-drip proof

PSI

pounds per square inch

PVC

polyvinyl chloride

rpm

revolutions per minute

SAE

Society of Automotive Engineers

SWT

sweat

UL

Underwriters Laboratory

wgt.

weight