Unit cabinet dimensions, Coil specifications, Dimensional drawings – Titus VAB IOM User Manual
Page 2: Vab installation manual

VAB Installation Manual
IOM-VAB-00
06-30-04
2 of 7
Figure 1. Air Handler Model Number
Nomenclature
Unit Cabinet Dimensions
Table 2 provides the cabinet dimensions for each VAB
model along with the blower-opening outlet.
Coil Specifications
Table 3 provides VAB model specifics for the chilled and hot
water coil outside diameter and shipping weight based on
the number of coils (weight for 4-row chilled water coil
includes weight for entire unit).
Dimensional Drawings
Figures 2 through 4 provide dimensional callouts with letters
corresponding to letters used in Tables 1 through 3.
Table 1. VAB Model Dimensions
Optional Discharge or Return Air Plenum
Dimensions (inches)
Model Nominal Rating in
Tons
Blower
Filter Size
(inches)
K
L
M
Shipping Wgt. (lbs.)
VAB08
2
9 x 9
20 x 20
22
23-1/2 12
23
VAB12
3
9 x 9
20 x 20
22
23-1/2 12
23
VAB16
4
10 x 10 22-1/2 x 22-1/2
25
23-1/2 14
30
VAB20
5
12 x 12
(2) 16 x 25
29-1/4 25-1/2 16
35
VAB30
7-1/2
15 x 15
(3) 16 x 25
39
27
24
41
VAB40
10
15 x 15
(4) 20 x 25
51-1/2
27
24
41
Table 2. Cabinet Dimensions
Cabinet Dimensions (inches)
Blower Opening
Outlet (inches)
Model
A
B
C
D E
F
G
H
J
K
VAB08
22
23-1/2
50
-
-
-
-
3
12
8-3/4
VAB12
22
23-1/2
50
-
-
-
-
3
12
8-3/4
VAB16
25
23-1/2
56-1/2
-
-
-
-
1-1/2
14
9-1/2
VAB20
29-1/4
23-1/2
59-5/8
-
-
-
-
1
14
13
VAB30
39
27
-
34 9
19-1/2
15-1/2
1
16-3/4
13-1/4
VAB40
51-1/2
27
-
34 9
19-1/2
20-1/2
1
16-3/4
13-1/4
Table 3. Coil Dimensions
4-Row Unit
2-Row Heating Coil
Model
Connection
Size
Shipping Wgt.
(lbs) Note 1
Connection
Size
Shipping Wgt.
(lbs) Note 2
VAB08
3/4" OD SWT
164
7/8" OD SWT
14
VAB12
3/4" OD SWT
170
7/8" OD SWT
14
VAB16
7/8" OD SWT
200
7/8" OD SWT
17
VAB20
1-1/8" OD SWT
253
1-1/8" OD SWT
21
VAB30
1-1/8" OD SWT
364
1-1/8" OD SWT
81
VAB40
1-3/8" OD SWT
462
1-1/8" OD SWT
102
Note 1: Weight for entire unit.
Note 2: Weight for heating coil only.