beautypg.com

Water piping, Installation of options, Discharge / return air plenum – Titus VAB IOM User Manual

Page 5: Condensate drain, Vab installation manual

background image

VAB Installation Manual

IOM-VAB-00

06-30-04

5 of 7

Condensate Drain

Install unit with 1/8-inch pitch toward condensate drain

opening.
Condensate drain must consist of a minimum of ¾-inch

copper tubing, ¾-inch galvanized pipe, or ¾-inch PVC

pipe. Figure 6 shows condensate drain setup. The drain

trap must be properly configured to ensure the removal of

all condensate runoff. Ensure drain pitches downward at a

slope of one inch every 10 feet.

Note 1: Incorrect trapping can hold water in pan,

causing overflow.
Note 2: Consult local codes for additional precautions

before installing condensate drain.

Water Piping

All piping must be supported, independent of coils. Swing

joints or flexible fittings must be provided to absorb

expansion and contraction strains. Rigid piping reduces

the effectiveness of vibration isolators. The water supply

should always be connected so the entering water is on

the leaving airside of the coil. Coils must be adequately

vented in order to prevent air binding.

Note 1: Freeze-ups due to low air temperatures are

not covered under the warranty agreement.
Note 2: Titus recommends a freeze-stat (by others) be

installed when a hot water coil is used and mounted in

the reheat position.

Installation of Options

In addition to the standard equipment, the following

optional equipment may require attention during

installation.

Discharge plenum.

Return air plenum.

Two-row hot water heating coil (reheat or preheat

location).

Electric heat.

Motor and drive selections.

Discharge / Return Air Plenum

The plenum can be used for either the discharge or return

air as shown in Figure 7. The construction consists of

three permanent sides and one removable panel attached

by screws. This panel may be removed to attach a grille

(not provided) or ductwork and then re-attached to the

plenum. If required, field technicians may choose to cut an

opening in one of the other three sides of the plenum.

Note: The contractor in the field determines the

opening size and location for the grille or ductwork

since they are field cut.

Figure 6. Condensate Drain

Figure 7. Optional Plenum Locations