12

Installation Manual - Underfloor Products

Underfloor Products IOM

Redefine your comfort zone. ™ | www.titus-hvac.com

Notes:
1. All referenced part numbers in the interconnect diagram below can be found on the TAF-R/TAF-R-FR ordering procedure
2. A maximum of six actuators may be daisy chained between the thermostat and transformer. After that, a maximum of six more actuators may be
daisy chained on the opposite side of the transformer. A maximum of 12 actuators may be supplied from one transformer and controlled from one
thermostat.
3. The transformer must have an internal circuit breaker or equivalent breaker or equivalent 2.25A external fuse in the secondary circuit.

Actuated TAF-R/TAF-R-FR Interconnect Wiring Diagram

Actuated TAF-R / TAF-R-FR Interconnect Wiring Diagram