beautypg.com

Pre - installation – Titus LSC IOM User Manual

Page 7

background image

Pre - Installation

Hazardous Voltage!
Disconnect all electric power, including remote disconnects
and discharge all motor start/run capacitors before
servicing. Follow proper lockout/ tagout procedures to
ensure the power cannot be inadvertently energized. For
variable frequency drives or other energy storing
components provided by Titus or others, refer to the
appropriate manufacturer’s literature for allowable waiting
periods for discharge of capacitors. Verify with an
appropriate voltmeter that all capacitors have discharged.
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious injury.

WARNING

Receiving and Handling

Upon delivery, inspect all components for possible
shipping damage. See “Receiving Checklist” (below) for
detailed instructions. Titus recommends leaving units and
accessories in their shipping packages/skids for protection
and ease of handling until installation.

Shipping Package

The LSC units are multi packed and ship in pallets for
handling and storage ease. Each Unit has tagging
information such as the model number, sales order
number, serial number, unit size, piping connections, and
unit style to help properly locate the unit in the floor plan. If
specified, the unit will ship with tagging designated by the
customer.

Receiving Checklist

Complete the following checklist immediately after
receiving unit shipment to detect possible shipping
damage.

Inspect individual pallets before accepting. Check for

rattles, bent corners, or other visible indications of
shipping damage.

If a unit appears damaged, inspect it immediately before

accepting the shipment. Manually rotate the fan wheel to
ensure it turns freely. Make specific notations concerning
the damage on the freight bill. Do not refuse delivery.

Inspect the unit for concealed damage before it is stored

and as soon as possible after delivery. Report concealed
damage to the freight line within the allotted time after
delivery. Check with the carrier for their allotted time to
submit a claim.

Do not move damaged material from the receiving

location. It is the receiver’s responsibility to provide
reasonable evidence that concealed damage did not occur
after delivery.

Do not continue unpacking the shipment if it appears

damaged. Retain all internal packing, cartons, and crate.
Take photos of damaged material.

Notify the carrier’s terminal of the damage immediately

by phone and mail. Request an immediate joint inspection
of the damage by the carrier and consignee.

Notify your Titus representative of the damage and

arrange for repair. Have the carrier inspect the damage
before making any repairs to the unit.

Compare the electrical data on the unit nameplate with

the ordering and shipping information to verify the correct
unit is received.

Jobsite Storage

This unit is intended for indoor use only. Store the unit
indoors to protect the unit from damage due to the
elements. If indoor storage is not possible, make the
following provisions for outdoor storage:

1. Place the unit(s) on a dry surface or raised off the
ground to assure adequate air circulation beneath unit and
to assure that no portion of the unit contacts standing water
at any time.

2.Cover the entire unit with a canvas tarp only. Do not use
clear, black or plastic tarps as they may cause excessive
moisture condensation and equipment damage.

Installation Preparation

Before installing the unit, consider the following unit
location recommendations to ensure proper unit operation.

1. Clearances: Allow adequate service and code
clearances as recommended in “Service Access” (the next
section). Position the unit and skid assembly in its final
location.
2.Structural support: Ensure the structural support is strong
enough to adequately support the unit. The installer is
responsible for supply support rods for installation of ceiling
units.
3.Level: To ensure proper unit operation, install the unit
level (zero tolerance) in both horizontal axes. Failure to
level the unit properly can result in condensate
management problems, such as standing water inside the
unit.

4.Condensate line & piping: Consider coil piping and

condensate drain requirements. Verify condensate line is
continuously pitched 1 inch per 10 feet of condensate line
run to adequately drain condensate.

TU-LSC-IOM

7