beautypg.com

Ffde, ffder, ffdera models fan filter unit iom – Titus FFDE/FFDER/FFDERA User Manual

Page 5

background image

I N S T A L L A T I O N & O P E R A T I O N M A N U A L

FFDE, FFDER, FFDERA Models

Fan Filter Unit IOM

Installation & Operation

Installation


Note: Titus fan filter units are completely assembled at the factory with the exception of the optional ¼”-20 eyebolts
that are used when hanging the unit from an engineered design support system and installation of the HEPA/ULPA filters
(eyebolts not included and can be ordered separately, p/n 222449-001).

Step 1.

Carefully remove the unit from the shipping carton and inspect for any damage that may have occurred during

transportation (See Figure 1).

5

Note: When ordering FFDER and
FFDERA units, the HEPA filters may
be shipped separately to be installed
into units after the fan box has been
installed.

Recommendation:
Review mode settings
at this time as specified
for installation
(see page 7 for controls).

Figure 1: Unboxing

If using rigidly supported grid (usually 2” (50 mm) or wider), raise unit through ceiling and lower onto the gasketed

grid. If using a flexible grid (typically supported with wires), the unit must be secured to an engineered design support

system with s-hooks and chain. Screw the four eyebolts into the nutserts on the lid assembly before lifting into an
overhead position (see Figure 2) Note: Confirm fan dimensions to match T-grid dimensions.

EYEBOLT

FAN FILTER
UNIT

Figure 2: Hanger Supports

Step 3.

Raise the unit and secure it into place using the chosen support system method suspended from a structural support

bracing.

Step 4.

Have an electrician wire the unit to the appropriate voltage, according to the wiring diagram (page 17), and all national

and local electrical codes. All units are equipped with a three position terminal block for field onnection. Verify correct singlephase
power, before energizing units.

Step 5.

Turn on the power using the two position rocker switch (ON/OFF) located on the electrical box. For FFDER and

FFDERA units, let the unit run for a few hours to purge off particulate (if filters are shipped loose) that may be adhered to
the inside of the unit before installing the filters. Do not run fan at full speed as this may cause overload condition.
Note: Your fan filter may have been shipped separate. Controls have been shipped separately.

Step 2.