Ffde, ffder, ffdera models fan filter unit iom – Titus FFDE/FFDER/FFDERA User Manual
Page 12

I N S T A L L A T I O N & O P E R A T I O N M A N U A L
FFDE, FFDER, FFDERA Models
Fan Filter Unit IOM
Installation & Operation
12
Motor Issues in Manual Mode:
(If you are in a network or analog mode, contact your controls contractor for troubleshooting assistance; if you continue to
need assistance, contact the factory.)
Unit is not adjustable:
Step 1.
Verify that rotation of the manual speed potentiometer does not change the RPM. If rotating does nothing, remove
the electrical box cover, then remove the 4-pin motor connector from the control board and reinstall 180 degrees rotated.
Also insure that the 4-pin connection wires are pushed down securely onto connector pins. Again adjust the knob to verify
proper fan operation. Note: The 4 pin connector is on the 1/8” white cable from motor.
Low Air Velocity:
Step 1.
Check to be sure that the manual speed potentiometer is set correctly.
Step 2.
Check incoming power supply for proper voltage (120,208-240,277/24).
Step 3.
Examine the HEPA filter.
High Air Velocity:
Step 1
. Check to be sure that the air flow settings are correct
Filter Issues:
Non-Laminar Flow and/or Excessive Contamination:
Step 1.
Insure that no large obstructions are upstream of airflow pattern
Step 2.
Determine that no other air-moving devices are operating in or around clean room which disrupt room’s
airflow pattern
Step 3.
Check air velocity and if low, conduct the “Low Air Velocity” procedure outlined above.
Step 4.
Conduct smoke and photometer test on HEPA/ULPA filter. Seal or replace HEPA filter as necessary.
Mode Choice:
Verify mode setting choice to DIP switch S1 (Control Mode), which is manual mode and then retry.
Troubleshooting
Net LED Status Definition
Green LED OFF
Power Lost or No Communications
Green LED Flickering
Network Data Traffic In Progres
Green LED ON
A/B network wires are swapped
Red Network LED
Green Status LED