Ffde, ffder, ffdera models fan filter unit iom, Installation & operation – Titus FFDE/FFDER/FFDERA User Manual
Page 11
I N S T A L L A T I O N & O P E R A T I O N M A N U A L
FFDE, FFDER, FFDERA Models
Fan Filter Unit IOM
Installation & Operation
COMMUNICATION SPECIFICATIONS
Overview:
• MODBUS RTU protocol over RS485 (serial)
• 9600 baud rate, word length is 8, parity is none(n), stop bits=1
• 255 unique address values selectable by DIP switch settings
• (recommended network node capacity 200 nodes)
• Slew rate limited transceivers for improved network performance MODBUS Register Summary Table
• DO NOT USE CROSSOVER CABLES. THIS MAY DAMAGE THE CONTROL CARD OR RENDER IT NON-OPERATIONAL.
11
MODBUS Register Specifications
Register
Name
R/W Values & Defaults
Units
Origin
Comments
1
RUN/STOP
RW
0,1
1
RAM
power up from REG 14
2
DEMAND
RW
0-100
%
RAM
power up from REG 10
6
SPEED
R
0,5-2000
RPM
LIVE
7
ANA1
R
0-1000
-
LIVE
Onboard Pot 0-1000=0-100%
9
STATUS
R
see detail
-
LIVE
10
DEFAULT SPEED
RW
0-100
50
EEPROM
applies to network only
12
CURRENT SPEED
R
0-100
-
LIVE
14
DEFAULT RUN/STOP
RW
0,1
1
EEPROM
applies in network mode only
24
ANA2
R
0-1000
-
LIVE
0-10V input 0-1000=0-10VDC
To reset non-volatile registers to factory default values, write 170 (AA hex) to Register 14, and then cycle power.
Note: Register 24 may be read in network mode to determine the value of 0-10VDC signal that may be connected.
For example, a pressure transducer may be connected to indicate unit interal static pressure.