I N S T A L L A T I O N & O P E R A T I O N M A N U A L

FFDE, FFDER, FFDERA Models

Fan Filter Unit IOM

Installation & Operation

COMMUNICATION SPECIFICATIONS

Overview:

• MODBUS RTU protocol over RS485 (serial)
• 9600 baud rate, word length is 8, parity is none(n), stop bits=1
• 255 unique address values selectable by DIP switch settings
• (recommended network node capacity 200 nodes)
• Slew rate limited transceivers for improved network performance MODBUS Register Summary Table

• DO NOT USE CROSSOVER CABLES. THIS MAY DAMAGE THE CONTROL CARD OR RENDER IT NON-OPERATIONAL.

11

MODBUS Register Specifications

Register

Name

R/W Values & Defaults

Units

Origin

Comments

1

RUN/STOP

RW

0,1

1

RAM

power up from REG 14

2

DEMAND

RW

0-100

%

RAM

power up from REG 10

6

SPEED

R

0,5-2000

RPM

LIVE

7

ANA1

R

0-1000

-

LIVE

Onboard Pot 0-1000=0-100%

9

STATUS

R

see detail

-

LIVE

10

DEFAULT SPEED

RW

0-100

50

EEPROM

applies to network only

12

CURRENT SPEED

R

0-100

-

LIVE

14

DEFAULT RUN/STOP

RW

0,1

1

EEPROM

applies in network mode only

24

ANA2

R

0-1000

-

LIVE

0-10V input 0-1000=0-10VDC

To reset non-volatile registers to factory default values, write 170 (AA hex) to Register 14, and then cycle power.

Note: Register 24 may be read in network mode to determine the value of 0-10VDC signal that may be connected.

For example, a pressure transducer may be connected to indicate unit interal static pressure.