Control Console Operation

User Mode

In user mode, the user can:
1) Select a unit with the select knob,
2) Adjust the set point of a unit with the adjust knob, and
3) Go into the options mode using the select knob.

Note: If ‘LO’ is shown in the Status Display, the network is
in standby mode and set points cannot be adjusted.

10

Standby/Monitor Mode


The control console immediately enters standby monitor mode at the conclusion of power-on scanning. The control console remains in
standby monitor mode until one of the two dials are rotated. If the dials are not adjusted for a period of 30 seconds, the control console will
revert to standby monitor mode.

In standby monitor mode, the control console repeatedly polls all units detected during power-on scanning. Unused motor addresses are
skipped, but the highest address must be within range of the control console model settings (25 or 125.)

ADDRESS

SET SPEED

PRESSURE SWITCH STATUS

ANY ROTATION

TO EXIT STANDBY

MONITOR MODE

STANDBY MONITOR MODE

FRONT PANEL FUNCTIONS

The following information is shown:

Address Display:
• MODBUS address of each unit

Status Display:
• ‘PG’ for pressure switch good
• ‘PF’ for pressure switch fault
• ‘ ‘ if no pressure switch is enabled
• ‘LO’ if network is in standby (setback) mode

Set Speed Display:
• Set speed of operation in percent of full motor speed

o Value read from MODBUS register 2


Note: If no response is received, the middle and lower LED shall display ‘—‘.

USER MODE

FRONT PANEL FUNCTIONS

ADDRESS

SET SPEED

PRESSURE SWITCH STATUS

ROTATE TO SELECT ADDRESS.

PRESS TO LOCK SELECTION.

NO EFFECT

If any dial activity is detected, the control console leaves standby monitor mode and enters user mode. In this mode, any unit can be selected
by

rotating

the

Select

Dial.


Note: If the Select dial is moved past the valid address range, the select display shows “OP.” Pushing the Select dial enters the Option Menu.