Installation, Gas pipe pressure testing, High elevation – Regency Liberty L390EB Medium Gas Insert User Manual
Page 19: Gas line installation, 885 s.i.t. valve description
L390E-2 / HZI390E-2 Direct Vent Gas Insert
19
installation
gas pipe pressure
testing
The appliance must be isolated from the gas sup-
ply piping system by closing its individual manual
shut-off valve during any pressure testing of the
gas supply piping system at test pressures equal
to or less than 1/2 psig. (3.45 kPa). Disconnect
piping from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
note: to properly check gas pressure, both
inlet and manifold pressures should be
checked using the valve pressure ports
on the valve.
1) Make sure the valve is in the "OFF" position.
2) Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a
1/8" wide flat screwdriver.
3) Attach manometer to "IN" and/or "OUT" pressure
tap(s) using a 5/16" ID hose.
4) Light the pilot and turn the valve to "ON" position.
5) The pressure check should be carried out with
the unit burning and the setting should be within
the limits specified on the safety label.
6) When finished reading manometer, turn off the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" flat screwdriver.
Note: Screw should be snug, but do not over
tighten.
HigH eleVatiOn
This unit is approved for altitude 0 to 4500 ft. (CAN1
2.17-M91).
gas line
installatiOn
Since some municipalities have additional local
codes it is always best to consult with your local
authorities and the CAN/CGA B149 installation
code.
For USA installations follow local codes and/or the
current National Fuel Gas Code, ANSI Z223.1.
When using copper or flex connectors use only
approved fittings. Always provide a union so that
gas lines can be easily disconnected for servicing.
Flare nuts for copper lines and flex connectors are
usually considered to meet this requirement.
note: a shutoff / dante valve should be sup-
plied in or near the unit (or as per local codes)
for ease of servicing this appliance.
impoRtant: always check for gas leaks with
a soap and water solution or gas leak detector.
Do not use open flame for leak testing.
l390e-2 ng / HZi390e-2 ng
systeM data
Min. Supply Pressure 5" WC (1.25 kpa)
Manifold Pressure
3.5" WC (0.87 kpa)
Orifice Size
#35 DMS
Maximum Input
31,000 Btu/h
(9.09 kW)
l390e-2 lp / HZi390e-2 lp
systeM data
Min. Supply Pressure 11" WC (2.73 kpa)
Manifold Pressure
10" WC (2.49 kpa)
Orifice Size
#53 DMS
Maximum Input
31,000 Btu/h
(9.09 kW)
note: if you have an incorrect flame pattern,
contact your regency
®
dealer for further
instructions.
incorrect flame pattern will have small, probably
yellow flames, not coming into proper contact
with the rear burner or flame sensor.
Burner
Flame Sensor
Pilot
Ignitor
885 s.i.t. ValVe
desCription
1) 6 Stage flame adjustment
2) Pilot adjustment
3) Outlet Pressure Tap
4) Inlet Pressure Tap
5) Pilot Outlet
6) Main Gas Outlet
7) Main Gas Inlet
1
2
3
4
6
5
7