L390E-2 / HZI390E-2 Direct Vent Gas Insert

installation

Air Shutters are required to increase or decrease the amount of air that is
mixed with the fuel before combustion. This will have an affect on how well
the fuel combusts and how the fl ame physically appears.
Low primary air will leave a taller, yellower fl ame while higher primary air will
leave a lower, bluer fl ame.

This setting is largely for appearance, however, not enough primary air may
lead to carboning, sooting or a fl ame that reaches the top of the fi rebox.
Situations that may require more primary air are; units that are burning
propane, units installed at higher elevations or units that are run on high
most of the time.

The L390E / HZI390E is equipped with an air shutter that is accessible from
outside the fi rebox and can be adjusted during operation.

Aeration adjustments should only be made after the unit has been on for 30
minutes to 1 hour.

Slide the Air Shutter Lever towards you to increase the primary air setting.

Slide the Air Shutter away from you to decrease the primary air setting.
Below you will see a chart showing the minimum primary air settings.

These are set from the factory, but due to fuel conversions or installation
conditions, the air setting may need to be adjusted.

Close

Open

unit

fuel type

min. air setting

L390E

NG

3/16" (5mm)

L390E

LP

1/4" (6mm)

HZI390E

NG

3/16" (5mm)

HZI390E

LP

1/4" (6mm)

air sHutter adjustMent

Air Shutter

Burner Mounting

Bracket

Gas Orifice

Air Shutter Lever

Firebox cut-away

to show location

of the Air Shutter

1) Slide the Air Shutter Lever towards you to increase the primary air set-

ting.

2) Slide the Air Shutter away from you to decrease the primary air setting.

Below you will see a chart showing the minimum primary air settings.

CAUTION: Carbon will be produced if air shutter is closed too much.

note: any damage due to carboning resulting from improperly setting
the aeration controls is not covered under warranty.

note: aeration adjustment should only be performed by an authorized

regency installer at the time of installation or service.

Push to close - Pull to open

Unit Front

Unit Back

First Fire & Aeration