Installation, Vertical termination with co-linear flex system – Regency Horizon HZ33CE Small Gas Fireplace User Manual
Page 22
22
Regency HZ33CE Gas Fireplace
INSTALLATION
Flex Liner
Exhaust
Flue
A maximum
of two certified
joiner kits
may be used
per length.
#948-305
35 ft (11m)
Air Intake
Co-linear DV
Vertical Termination
Cap # 946-529
Co-Linear
Flex
Adapter
with Kit#
946-563
Outer
Pipe
with Kit#
946-563
Inner Pipe
Adapter
with Kit#
946-563
Rigid Pipe Adaptor
# 510-994
Pipe Length
45 Elbow
o
VERTICAL TERMINATION
WITH CO-LINEAR FLEX SYSTEM
This appliance is designed to be attached to
two 3" (76mm) co-linear aluminium fl ex running
the full length of the chimney. See the "Venting
Arrangements - Vertical Terminations" Section
for minimum and maximum heights.
Required Parts:
Part #
Description
946-529 Co-linear
DV
Vertical
Termination
Cap
948-305
3" Flex - 35 ft.
946-563
Co-Axial to Co-Linear Adapter Kit
which contains the following:
Co-linear Flex Adapter
Outer
Pipe
Inner Pipe Adapter
510-994
Rigid Pipe Adaptor
46DVA-E45 45
o
Elbow
Alternate Approved Caps
46DVA-VC Vertical Termination Cap
46DVA-VCH High Wind Cap
46DVAGK 3" Co-linear Adapter with fl ashing
Masonry chimneys may take various contours which the fl exible liner will accommodate. However,
keep the fl exible liner as straight as possible, avoid unnecessary bending.
The Air Intake pipe must be attached to the inlet air collar of the termination cap.
THE APPLIANCE MUST NOT BE
CONNECTED TO A CHIMNEY FLUE
SERVING A SEPARATE SOLID FUEL
BURNING APPLIANCE.