FPI FP90 Wood Fireplace

9

INST

ALLA

TION

no combustibles on face of unit.
combustibles May not extend to

unit face.
do not notch wallboard around

standoffs.

The FP90 may be placed on or near construction

materials. The combustion air kit, fire stop spacer

and roof flashings (not chase flashings) may be

placed directly on or against normal construction

materials. The chimney requires a minimum 2"

(51mm) clearance. A combustible mantle (to a

depth of 10", 254mm) may be installed no closer

than 18" (457mm) above the warm air vent or

55-1/2" (1410mm) from bottom of unit.

The chimney must be enclosed when installed

in or passing through a living area where

combustible material or people may come in

contact with it. This is important to prevent

possible personal injury or fire hazard.

For any further information, please call your

dealer. Special restrictions apply to the front

and facing of the fireplace and nearby walls.

WarninG: If insulation is used, do not place

the unit against it. Insulation or vapor barriers, if

used, must be secured to assure insulation and

vapor barriers remain in place and do not affect

the required air spaces.

WarninG: Do not pack or fill required air spaces

with insulation or other material. No material of

any kind is allowed in these areas.

notes:

1) Do not insulate the chase cavity with blown

or fill type insulation materials.

2) Local codes may not require firestopping

at the ceiling level for outside chase

installations; however, it is recommended

for safety and the reduction of heat loss.

3) We recommend that you insulate at least the

first floor of the chase to prevent heat loss.

4) Some local codes require 1 hour fire rating

on one or all sides of fire chases. Check with

your local authorities.

clearances and HeiGHt reQuireMents

installation

Clearances to Combustibles

Max. 10" (254mm)

Depth of Mantel

center line

18" (457mm)

55-1/2" (1410mm)

from bottom of unit

18" (457mm)

20" (508mm)

40" (1016mm)