Heatwave kit (not epa approved), Minimum framing clearances, Installation – Regency Excalibur EX90 Large Wood Fireplace (Canadian Edition) User Manual

Page 33: Minimum duct clearances

background image

FPI FP90 Wood Fireplace

33

HEA

TW
A

VE KIT

HeatWaVe Kit (not epa approVed)

MiniMuM fraMinG

clearances

* Wall studs must be 16" on center for

mounting fan housing.

* Fan Housing: Maintain a 1/4" (6mm)

clearance from fan housing to combustible

material.

* Wall Registers must be 4"(102mm) from

floor above or ceiling below.

Minimum duct clearances

The air duct has a '0' clearance to

combustible. The first 60" of pipe from

the unit must be covered with insulation.

(Insulation included with kit.)

2) Remove the knock-out and bend the tabs

outward.

installation

note: Installation of Heat Wave duct kit should

be done prior to drywall installation.

a) r90 / eX90 Models:

1) Remove the cover plate from the fireplace

side and discard.

Remove the 2 screws holding the cover plate

on the fireplace side.

note: this must be done prior to placing

fireplace into final position.

Center Round Duct

collar over hole and

attach to the tabs

using 3 screws

B) all Models:

1) Determine the location of the air register/fan

housing assembly. Cut a 5" x 16" (121mm

x 406mm) hole between framing members

(wall studs or floor joists). Maintain a

1/4" (6mm) clearance from fan housing

to combustible material. See Framing

Clearances section.

2) Mount and secure the fan housing assembly

to framing members, the front of the fan

housing will protrude 1/2" (51mm) out of

the wall so it may be finished with drywall,

etc. See diagram 2 below.

Diagram 2: Side View - Secure fan housing

to minimum 2 x 4 framing.

Diagram 1:

Front View

3) Install the air duct run. Secure the duct to the

duct collar on the unit and to the fan housing

with 3 screws (per end) and aluminum duct

tape (UL 181A-P or equivalent).

the first 60" of duct pipe (from the unit)

must be covered with insulation.

round air duct: Attach the 6" round air

duct (supplied) to the fireplace collar and

run the duct to the fan housing. Attach the

round-to-oval adaptor to the fan housing

and the air duct to the adaptor.