Ventilated Chase Pan

Before You start

Check your inventory list to be sure you have all the necessary parts supplied in good usable

condition. Check for any concealed damage. Check the operation of the combustion air damper.

When the damper is in the fully closed position, the damper handle should be to the left. When

damper is in the fully open position, the damper handle must be in the right position.

installation coMponents diaGraM

installation components

note: insulation does not come in contact

with chimney. Maintain a 2" (51mm)

clearance.

installation

cHiMneY sYsteM

considerations

Regency’s FP90 Fireplace is to be installed

with one of the following Chimney Systems

only. Chimney systems only 7" (178mm) or 8"

(203mm) diameter are to be used.

in canada

Any of the following ULCS 629 listed chimney

systems may be used:

1) CF Sentinal

2) SuperPro 2100+

3) SuperVent 2100+

4) Security S-2100+

5) Oliver Macleod HT6000+

6) Dura Plus HTC

7) ICC Excel 2100

note: 8" (203mm) - 7" (178mm) adapter is

mandatory for installation using 7" (178mm)

chimney. anchor plate must be purchased

with selected chimney system from chimney

supplier.

The use of only one of these systems is permitted

when installing the fireplace. Do not alter or mix

parts from other systems as this may cause a

potential hazard and void Regency’s limited

warranty.

chimney Height

The total height of your chimney system from the

top of the fireplace to the chimney cap must not

exceed 40'(12m), and must also meet minimum

system height requirements. Please refer to

the flue manufacturer's instructions for specific

details. Refer to Minimum Recommended Flue

Height section.

chase enclosure

A chase is a vertical box-like structure

constructed to surround the fireplace and

chimney. A ventilated chase cap is highly

recommended. Refer to flue manufacturer's

instructions for reduced flue heights above chase

terminations. As with all chimney installations,

avoid overhead obstructions such as trees,

power lines, etc.

A chase should be constructed just like any out-

side wall, insulated and vapor barriered. Please

check with local building authorities. In a cold

climate, we recommend the base of the chase

be insulated between the solid continuous floor

beneath the fireplace and the chase bottom. If

used, the value and amount of chase insulation

in a cold climate installation is optional and not

required for safety. Insulation is recommended

to avoid heat loss.

Insid

e W

all

Rain Cap

Storm Collar

Roof Flashing

Attic Radiation

Shield

Nailing Strip

Outside Fresh

Air Duct

Hearth

Extension

Hearth Safety

Strip

Outside Air

Inlet

Framing