beautypg.com

Return-to-normal alarm messages, Network service disruption – Sensaphone WEB600 Users manual User Manual

Page 33

background image

33

Chapter 6: operation

The reset time must be set high enough to allow all enabled escalation levels to be notified about an

alarm before it is reset.
Sample Alarm Message – (E-mail format):

From:
Sensaphone WEB600
ACME Widgets Monitoring System
Oak & Pine St - Hatfield, PA

High Alarm detected on Zone 1: Server Room Temp
Alarm occurred on Sunday, February 8, 2009 at 9:18:27pm
It is now 87.1F
Level crossed limit of 85.0F

retUrn-to-norMal alarM MessaGes

If a zone is programmed with the Return-to-Normal option enabled, then a message will be sent to

those profiles/Contacts that were sent the original alarm message, informing them that the condition

has gone back to a normal condition. Those Profiles/Contacts that did not receive the original alarm

message due to Scheduling, Escalation or Network Service Disruption will not receive the Return-to-

Normal message.

network serViCe disrUption

In the event that the Ethernet network (or e-mail server) becomes unavailable due to a service disrup-

tion or power failure, the WEB600 will hold the current alarm messages until service is restored, how-

ever, if both power and battery fail or the alarm no longer exists before the network services are restored

then the alarm messages will be lost.