Chapter 1: installation

norMally open / norMally Closed dry ContaCts

Dry contact sources consist of alarm relays or switches that are isolated and have no external volt-

age applied. These devices can be connected directly to the zone terminals without regard for polarity.

Choose a zone and connect the wires to the corresponding screw terminals for that zone. The following

figure shows how to connect a dry contact sensor:

Wiring a Dry Contact Sensor

2.8k/10k teMperatUre sensors

The Web600 is compatible with 2.8K/10K temperature sensors that match the curve data listed in the

tables in Appendix F. The monitoring temperature range of the 2.8K thermistor is -109 to 115ºF (-85º

to 57ºC) and the 10K thermistor is -87° to 168°F (-66° to 76°C). Temperature sensors can be connected

directly to the zone terminals without regard for polarity. Choose an input and connect the wires to

the corresponding screw terminals for that zone. 2.8K and 10K temperature sensors are available from

Sensaphone. See Appendix C for part numbers. The figure below shows how to connect a temperature

sensor:

Wiring a Temperature Sensor