WEB600 User’s Manual
reset the datalogger
bit
TrUE
0x00257
reset the eventlogger
bit
TrUE
0x00258
system time (string)
string
any Time >= 2009
3x00256
Modbus® noTes
ModbUs® addresses
address ranges
The Modbus® address ranges are laid out according to the following color-coded table.
The format below is TxDDDDD where “T” is the address type (bit/word, read-write/
read-only) and DDDDD is a 5 digit decimal base number from 0 to 65535.
Modbus® Mode
Modbus® Address Range
bit, read-write
0x00000 - 0x65535
bit, read-only
1x00000 - 1x65535
word, read-only
3x00000 - 3x65535
word, read-write
4x00000 - 4x65535
The memory types map to the Modbus® commands as shown in the following table.
The Web600 supports Modbus® conformance classes 0 and 1.
Address Type Modbus® Commands
0
1, 5, 15
1
2
3
4
4
3, 6, 16
address Calculation
Modbus® Address calculations are performed according to the following table:
Type
Calculation
Notes
Zones
BasE + (oFFsET * inpUT_nUMBEr)
The input number is as follows:
Zone 1 = 2
Zone 2 = 3
Zone 3 = 4
Zone 4 = 5
Zone 5 = 6
Zone 6 = 7
power = 0
Battery = 1
output
BasE+(oFFsET*oUTpUT_nUMBEr)
output=1
profiles
BasE + (oFFsET * proFilE_nUMBEr)
The profile number is as follows:
profile 1 = 0
profile 2 = 1
profile 3 = 2
profile 4 = 3
profile 5 = 4
profile 6 = 5
profile 7 = 6
profile 8 = 7