30

Parameter

Full Scale @ Input
Range

Accuracy

Range

% Reading

% FS

Conditions

Reactive energy

1

Import & Export

Accuracy Class 0.2%

0 to 999,999.999 Mvarh

Apparent energy

1

Accuracy Class 0.2%

0 to 999,999.999 MVAh

Volt-hours

Class 0.2

20% - 120% FS

0 to 999,999.999 kVh

Ampere-hours

Class 0.2

10% - 200% FS

0 to 999,999.999 kAh

Symmetrical
components

Voltage FS

Current FS

Current FS

1

1

3

10% - 120% FS

10% - 200% FS

200% - 2000%FS

Phasor angles

1 degree

Key: PT - external potential transformer ratio

@ 80% to 120% of voltage FS and 1% to 200% of

current FS

CT - primary current rating of external current transformer

FSV - voltage full scale;

FSI - current full scale

Vf- fundamental voltage; If - fundamental current

Notes

1. Accuracy is expressed as ± (percentage of reading + percentage of full scale) ± 1 digit. This does not
include inaccuracies introduced by the user's potential and current transformers. Accuracy calculated at 1
second average.

2. Specifications assume: voltage and current waveforms with THD ≤ 5% for kvar, kVA and PF; reference
operating temperature: 20°C - 26°C.

3. Measurement error is typically less than the maximum error indicated here.

1

Specified Accuracy Class Only for PM180-5A and PM180-1A models (internal CT), for PM180-

DFR model accuracy meets class 1