PM180 Substation Automation Unit
29
5.12 Measurement Specifications
Parameter
Full Scale @ Input
Range
Accuracy
Range
% Reading
% FS
Conditions
Voltage V1-V4
120VxPT @ 120V
400VxPT @ 690V
0.05
0.01
10% to 120% FS
0 to 99,999,999 V
Line current I1- I4
CT
0.05
0.05
0.2
0.01
0.01
For ANSI C12.20:
1% - 120% FS
120% - 400% FS
For IEC 62053-22:
1% - 200% FS
0 to 29,999 A
Fault current I1- I4
CT
2.0
400% - 2000% FS
0 to 29,999 A
DC Voltage
125V/220V
0.3
10% - 120%FS
0 to 290VDC
Active power
0.36×PT×CT @
120V
1.2×PT×CT @
690V
0.2
0.002
0.002
|PF| ≥ 0.5 and
-2,000,000 to +2,000,000 kW
Reactive power
0.36×PT×CT @
120V
1.2×PT×CT @
690V
0.3
0.002
0.002
|PF| ≤ 0.9 and
-2,000,000 to +2,000,000 kvar
Apparent power
0.36×PT×CT @
120V
1.2×PT×CT @
690V
0.2
0.002
0.002
|PF| ≥ 0.5 and
0 to 2,000,000 kVA
Power factor
1.000
0.35
|PF| ≥ 0.5,
I ≥ 2% FSI
-0.999 to +1.000
Frequency
0.002
40.00 Hz to 70.00 Hz
Total Harmonic
Distortion, THD
V (I), %Vf (%If)
999.9
1.5
0.2
THD ≥ 1% FS,
V (I) ≥ 10% FSV (FSI)
0 to 999.9
Total Demand
Distortion, TDD, %
100
1.5
TDD ≥ 1% FS,
I ≥ 10% FSI
0 to 100
Active energy
1
Import & Export
Class 0.2 ANSI C12.20-2002
Current class 20
Class 0.2S (IEC 62053-22)
0 to 999,999.999 MWh
1
Specified Accuracy Class Only for PM180-5A and PM180-1A models (internal CT), for PM180-
DFR model accuracy meets class 1
2
This accuracy specification is available from PM180 firmware version V31.XX.8 and can be
displayed from RGM180 software version V22.1.5