beautypg.com

5 plug-in i/o ratings – SATEC PM180 Installation Manual User Manual

Page 26

background image

PM180 Substation Automation Unit

23

Wire Size: 10 AWG (2.5 to 6 mm

2

)

Terminals Pitch: 9.5 mm

5.5 Plug-In I/O Ratings

Digital Inputs – 16 Inputs (up to 3 Modules)

Scan time: 1 ms @ 60Hz, 1.25 ms @ 50Hz.

16 optically isolated, dry contact sensing (voltage-free):

Internal power supply 24 VDC

Sensitivity: open @ input resistance >16kOhm, closed @ input resistance <10kOhm

Wire Size: 12 AWG (up to 2.5 mm

2

)

Terminals Pitch: 3.81 mm

16 optically isolated, wet contact sensing:

External Power Supply: 24 VDC

Sensitivity: open @ input resistance >16kOhm, closed @ input resistance <10kOhm

Wire Size: 12 AWG (up to 2.5 mm

2

)

Terminals Pitch: 3.81 mm

16 optically isolated, wet contact sensing:

External Power Supply: 48 VDC

Wire Size: 12 AWG (up to 2.5 mm

2

)

Terminals Pitch: 3.81 mm

16 optically isolated, wet contact sensing:

External Power Supply: 125 VDC

Wire Size: 12 AWG (up to 2.5 mm

2

)

Terminals Pitch: 3.81 mm

16 optically isolated, wet contact sensing:

External Power Supply: 250 VDC

Wire Size: 12 AWG (up to 2.5 mm

2

)

Terminals Pitch: 3.81 mm

Relays - 8 Outputs (up to 3 Modules)

8 relays - SPST Form A

Contact rating:

10A @ 250V AC, 5A @ 30V DC

0.25A @ 250V DC (sw. Volt.)

5A 250V DC (sw. Cur.)

Wire Size: 12 AWG (up to 2.5 mm

2

)

Terminals Pitch: 3.81 mm

Update time: 1/2 cycle

Analog I/O – 4 Inputs, 4 Outputs (up to 3 Modules)

4 Analog Inputs:

Ranges (upon order):

±

1 mA (100% overload)

0-20 mA

4-20 mA

0-1 mA (100% overload)