PM180 Substation Automation Unit

27

5.11 Standards Compliance

Directive complied with: EMC: 89/336/EEC as amended by 92/31/EEC and 93/68/EEC

LVD: 72/23/EEC as amended by 93/68/EEC and 93/465/EEC

Harmonized standards to which conformity is declared: EN55011:1991; EN50082-1:1992; EN61010-1:1993;
A2/1995

ANSI C37.90.1 Surge Withstand Capability (SWC)

EN50081-2 Generic Emission Standard - Industrial Environment

EN50082-2 Generic Immunity Standard - Industrial Environment

EN55022: Class A

IEC61000-6-2

IEC61000-6-4

IEC60255-5

IEC60255-22

Accuracy

Active Energy, IEC/AS 62053-22, class 0.2S

1

Reactive Energy, class 0.5S (under conditions as per IEC 62053-22:2003 @ 0≤ |PF| ≤ 0.9)

Power Quality

EN50160: Power Quality in European Electricity Supply Networks

IEEE 1159: Power Quality Recorder in US

GOST 13109: Electric energy, Electromagnetic compatibility of technical equipment, Power quality limits in
public electrical systems

GOST 54149: 2010: Electric energy, Electromagnetic compatibility of technical equipment, Power quality
limits in public electrical systems

IEC61000-4-7, Harmonics and inter-harmonics measurement

IEC61000-4-15, Flicker measurement

IEC61000-4-30 class A, Power quality measurement methods

IEC 62054-21: Real time clock backup, RTC accuracy ± 2ppm @ 23°C

EMC Immunity:

IEC61000-4-2, IEC60255-22-2: Electrostatic discharge, 15kV/8kV – air/contact

IEC61000-4-3, IEC60255-22-3: Radiated Immunity, 10V/m and 30V/m @ 80 MHz – 1000 MHz

IEC61000-4-4, IEC60255-22-4: Fast Transients burst, 4KV on current and voltage circuits and 2 KV for
auxiliary circuits

IEC61000-4-5, IEC60255-22-5: Surge 6KV on current, voltage circuits and power supply

IEEE C62.41.2-2002: high voltage line surges,

1

Only for PM180-5A and PM180-1A models (internal CT), PM180-DFR model accuracy

meets class 1