PM180 Substation Automation Unit
28
100 kHz ring wave – 6kV @ 0.5kA
1.2/50 microsecond – 8/20 microsecond Combination Wave – 6kV @ 3kA
IEC61000-4-6, IEC62052-11: Conducted Radio-frequency, 10V @ 0.15 MHz – 80MHz
IEC61000-4-8: Magnetic Field
IEC61000-4-12, IEC62052-11, IEEE C37.90.1: 2002: Oscillatory waves, CMM 2.5KV and DFM 1KV @
100KHz and 1MHz
Emission (radiated/conducted)
EN55022, IEC60255-22: Class A
Construction
Safety
IEC/UL 61010-1
Insulation
IEC62052-11: Insulation impulse 6KV/500Ω @ 1.2/50 µs
IEC62052-11, IEC61010-1: AC voltage tests related to ground, 4 KV AC @ 1mn
Atmospheric Environment
Operational ambient temperature range: –30°C to +70 °C
Long-term damp heat withstand according to IEC 68-2-3 <95%, +40 °C
Transport and storage temperature range: –40°C to +85 °C
Vibration
IEC 60255-21-1: Vibration Response, Table I, Class-2
IEC 60255-21-1: Vibration Endurance, Table II, Class-1
Mechanical Shock
IEC 60255-21-2: Shock, Table II, Class-1
IEC 60255-21-2: Bump, Table III, Class-1
Seismic Vibration
IEC 60255-21-3: Bump, Table III, Class-1
Panel Display protection
IEC 60529: IP54 (NEMA type 13)
Instrument protection
IEC 60529: IP30 (NEMA type 13)