PM180 Substation Automation Unit

25

Withstanding Insulation: 4kV AC @ 1 mn

Connector Type: RJ45 modular.

Supported Protocols: MODBUS TCP (Port 502), DNP 3.0/TCP (Port 20000), IEC 61850

Number of simultaneous connections (sockets): 5.

ETH2 - 10/100 TX- 100 FX (Communication Module)

Transformer-isolated 10/100Base-T port

Connector Type TX port: RJ45 modular

Optical-isolated 100Base FX

Connector Type FX port: SC

Supported Protocols: MODBUS TCP (Port 502), DNP 3.0/TCP (Port 20000), IEC 61850

Number of simultaneous connections (sockets): 5.

ETH2 - WiFi (Communication Module - future)

Wireless IEEE 802.11b/g

Withstanding Insulation: 4kV AC @ 1 mn

Connector Type WiFi port: SMA

Connector Type TX port: RJ45 modular

Supported Protocols: MODBUS TCP (Port 502), DNP 3.0/TCP (Port 20000), IEC 61850

Number of simultaneous connections (sockets): 5.

COM5 - MODEM (Communication Module - future)

Transformer-isolated internal 56K modem.

Withstanding Insulation: 2.5kV AC @ 1 mn

Connector Type: RJ11.

Supported Protocols: MODBUS RTU/ASCII, DNP 3.0

COM5 - CELLULAR (Communication Module - future)

2G/3G MODEM

Withstanding Insulation: 2.5kV AC @ 1 mn

Connector type: SMA

Supported Protocols: MODBUS TCP (Port 502), DNP 3.0/TCP (Port 20000)

Infrared (RGM180)

Optional optical IEC/ANSII head

Baud Rate: up to 115,200 bps.

Supported Protocols: MODBUS RTU/ASCII, DNP 3.0

5.7 Real-time Clock

Accuracy: maximum error 5 seconds per month @ 25

°

C

5.8 IRIG-B (Communication Module)

Optically isolated IRIG-B port

Withstanding Insulation: 4kV AC @ 1 mn

Time code signal: non-modulated (pulse-width coded).

Level: unbalanced 5V.

Connector Type: BNC.

Recommended cable: 51Ohm low loss - RG58A/U (Belden 8219 or equivalent), TNC connector

Recommended GPS time code generator: Masterclock GPS-200A