PM180 Substation Automation Unit
21
Appendix: Technical Specifications
5. Appendix: Technical Specifications
5.1 Environmental Conditions
Operating Temperature: -30°C to 70°C (-22°F to 158°F)
Storage Temperature: -40°C to 85°C (-40°F to 185°F)
Humidity: 0 to 95% non-condensing
Altitude ≤ 2000m
5.2 Construction
Overall Dimensions
Width: 220.00 mm (8.66 Inches)
Height: 152 mm (5.98 Inches)
Depth: 210.00 mm (8.26 Inches)
Weight: 2.5kg (5.51 Lb)
Materials
Enclosure: Polycarbonate
Panels: Polycarbonate
PCB. : FR4 (UL94-V0)
Terminals: PBT (UL94-V0)
Connectors-Plug-in type: Polyamide PA6.6 (UL94-V0)
Packaging Case: Carton and Stratocell (Polyethylene Foam) Brackets
Labels: Polyester film (UL94-V0)
5.3 Power Supply
Main Power Supply
Withstanding Insulation: 4kV AC @ 1mn
AD/DC Power Supply (standard): L/+, N/- and GND
Rated input: 50-290VAC 50/60 Hz, 90-290VDC, Maximum Power 10W
Wire Size: up to 10 AWG (up to 6 mm
2
)
Terminals Pitch 7.5 mm, three pins
Auxiliary Power Supply (module)
Withstanding Insulation: 4kV AC @ 1mn
AC/DC Power Supply: L/+, N/- and GND
Rated input: 50-290VAC 50/60 Hz, 40-290VDC, Maximum Power 20W
Low DC/DC Power Supply (option): (+), (-) and GND
12/24 VDC Option: Rated input 9.6-35 VDC, Maximum Power 20W
Wire Size: up to 10 AWG (up to 6 mm
2
)
Terminals Pitch 7.5 mm, three pins