beautypg.com

Appendix: technical specifications, 1 environmental conditions, 2 construction – SATEC PM180 Installation Manual User Manual

Page 24: 3 power supply

background image

PM180 Substation Automation Unit

21

Appendix: Technical Specifications

5. Appendix: Technical Specifications

5.1 Environmental Conditions

Operating Temperature: -30°C to 70°C (-22°F to 158°F)

Storage Temperature: -40°C to 85°C (-40°F to 185°F)

Humidity: 0 to 95% non-condensing

Altitude ≤ 2000m

5.2 Construction

Overall Dimensions

Width: 220.00 mm (8.66 Inches)

Height: 152 mm (5.98 Inches)

Depth: 210.00 mm (8.26 Inches)

Weight: 2.5kg (5.51 Lb)

Materials

Enclosure: Polycarbonate

Panels: Polycarbonate

PCB. : FR4 (UL94-V0)

Terminals: PBT (UL94-V0)

Connectors-Plug-in type: Polyamide PA6.6 (UL94-V0)

Packaging Case: Carton and Stratocell (Polyethylene Foam) Brackets

Labels: Polyester film (UL94-V0)

5.3 Power Supply

Main Power Supply

Withstanding Insulation: 4kV AC @ 1mn

AD/DC Power Supply (standard): L/+, N/- and GND

Rated input: 50-290VAC 50/60 Hz, 90-290VDC, Maximum Power 10W

Wire Size: up to 10 AWG (up to 6 mm

2

)

Terminals Pitch 7.5 mm, three pins

Auxiliary Power Supply (module)

Withstanding Insulation: 4kV AC @ 1mn

AC/DC Power Supply: L/+, N/- and GND

Rated input: 50-290VAC 50/60 Hz, 40-290VDC, Maximum Power 20W

Low DC/DC Power Supply (option): (+), (-) and GND

12/24 VDC Option: Rated input 9.6-35 VDC, Maximum Power 20W

Wire Size: up to 10 AWG (up to 6 mm

2

)

Terminals Pitch 7.5 mm, three pins