MTS Multi-Pump Control Manager User Manual
Page 29
![background image](/manuals/567994/29/background.png)
Status Screen
Multi-Pump Control Manager
Operation
29
8
Status
Indicator: Indicates the state of the associated module.
Status - gray: Label.
Not Present - light gray: Indicates the module is not present.
Ready- green: Indicates the module is present but is not enabled.
Enabled - green: Indicates the module is enabled and is ready to
into a run condition (replaces READY).
Running Low- green: Indicates the associated pump module is
running in low pressure.
High Pressure - green: Indicates the associated pump module is
running in high pressure.
Overload - red: Indicates an overload condition exists and a fault
is active for the associated module
Sequence - red: Indicates that the PLC commanded the motor
contactor to close, but the contactor did not close after a 10 second
time period and a fault is active.
9
Hours
Indicator: Indicates the running time in hours of the associated
module.
Hours - gray: Label.
Value - gray: The number of total hours the associated module has
been running.
10
Mute
Pushbutton: Allow you to mute the light buzzer if a fault or alarm
activates.
11
Stop Relay Indicator
Indicates whether the MPCM's safety relay is tripped.
E-Stop Relay - gray - OK: indicates the MPCM's safety relay has
not tripped.
E-Stop Relay - red - Fault: Indicates that the MPCM's safety relay
has tripped.
The cause of a safety relay trip is either an External E-Stop
Button, an HPU E-Stop Button, or an HPU Watchdog timer.
12
HMI E-Stop Indicator
Indicates whether the HMI E-Stop Button has been pressed.
HMI E-Stop - gray - OK: Indicates that the HMI E-Stop button has
not been pressed and is in the reset (closed) state.
HMI E-Stop - red - Fault: Indicates that the HMI E-Stop Button
has been pressed and is in the open state.
13
External E-Stops
Pushbutton Indicator
Indicates whether an external E-Stop chain has been pressed. User
defined text.
Text - gray - OK: Specific external e-stop chain does not have a
button that has been pressed and is in the reset (closed state).
Text - red - Fault: Indicates that the specific external e-stop chain
has an e-stop button that has been pressed, and is in the open state.
Item Name