9400 Technology applications | Table positioning
Parameter setting & configuration
Parameterisable function blocks
46
L
EDS94TA10050xxxx EN 1.2 - 03/2010
5.14.8
L_SdSwitchPoint1
5.14.9
LimitFollowingError1
5.14.10
LimitFollowingError2
Is an instance of
Function
L_SdSwitchPoint
Position switch points (cams)
Parameter
Possible settings
Information
C04395/1...8
State of switching range 1 ... 8
• Read only
0 Switch is off
1 Switch is on
C04396
String of digits
Position unit
• Read only
C04397/1...8
-2147483648
unit
2147483648 Switch-on position switching range
1 ... 8
C04398/1...8
-2147483648
unit
2147483648 Switch-off position switching range
1 ... 8
C04399/1...8
Enable switching range 1 ... 8
0 Switching range not enabled
1 Switching range enabled
Is an instance of
Function
L_SdSetPosition
Conversion of the following error switching threshold 1 selected in the real units of
the machine via C03911 into a position in [increments].
Following error monitoring ( 28)
Parameter
Possible settings
Information
C03911
-214000.0000
unit
214000.0000 Position value
• Initialisation: 100.0000 unit
C03912
String of digits
Position unit
• Read only
C03913
-2147483647
2147483647 State
• Read only
Is an instance of
Function
L_SdSetPosition
Conversion of the following error switching threshold 2 selected in the real units of
the machine via C03914 into a position in [increments].
Following error monitoring ( 28)
Parameter
Possible settings
Information
C03914
-214000.0000
unit
214000.0000 Position value
• Initialisation: 200.0000 unit