7 manual jog, 9400 technology applications | table positioning, Parameter setting & configuration manual jog – Lenze E94AxHE Technology Application Table positioning User Manual
Page 29
![background image](/manuals/566323/29/background.png)
EDS94TA10050xxxx EN 1.2 - 03/2010
L
29
9400 Technology applications | Table positioning
Parameter setting & configuration
Manual jog
5.7
Manual jog
[5-10] Basic function "Manual jog" (schematic diagram)
Parameter setting: Tab Application parameters dialog level Overview Manual jog
For the setting-up operation and
"Teaching" of positions the basic function
"Manual jog" is available.
Manual jog is controlled via parameters
(e. g. via HMI).
Manual jog can always be carried out if the
sequence control is not active and no other
basic function and no error status are
active. The request of manual jog then is
effected automatically with the travel
commands.
LS_ManualJog
n
t
и
з
LS_Brake
n
t
LS_Limiter
n
t
LS_Quickstop
STOP
n
t
LS_Stop
internal
status machine
Status
machine
(basic drive
functions)
Basic drive functions
M
0
-100
100 200
LS_Homing
n
t
LS_Positioner
Parameter
Lenze setting
Value Unit
C02620
Manual jog: Speed 1
360.0000 unit/s
C02621
Manual jog: Speed 2
720.0000 unit/s
C02622
Manual jog: Acceleration
360.0000 unit/s
2
C02623
Manual jog: Deceleration
1440.0000 unit/s
2
C02624
Manual jog: S-ramp time
0.100 s
C03007
Activate positive manual jog
FALSE
C03008
Activate negative manual jog
FALSE
C03009
Activate "Retract limit switch"
FALSE
Control inputs of the function
Signal configuration
Lenze setting
Control input
(Multiplexer parameters)
Automatic
activation
Request manual jog
C03155/1
C03007 Activate positive manual jog
C03155/2
C03008 Activate negative manual jog
C03155/3
FALSE Activate 2. speed
C03155/4
C03009 Activate "Retract limit switch"
C03155/5
+100 % Manual jog override
C03186/5