Troubleshooting and fault elimination – Lenze TML Flux Vector Drive 0.25kW-2.2kW User Manual
Page 24

22
Lenze 13466187 EDBTL03 v8
EN, DE, FR, IT, ES
Troubleshooting and fault elimination
Error
Cause
Remedy
(1)
JF
Remote keypad fault
Remote keypad disconnected
Check remote keypad connections
n1d
Drive identification fault
Attempt was made to perform motor
calibration before setting C86...C91
Must set C86...C91 before performing
motor calibration (see c48)
0C1
Short-circuit or overload
Short-circuit
Find reason for short-circuit; check
motor cable
Excessive capacitive charging
current of the motor cable
Use shorter motor cables with lower
charging current
Acceleration time (C12, c01) too short
• Increase acceleration time
• Check controller selection
Defective motor cable
Check wiring
Internal fault in motor
Check motor
Frequent and long overload
Check controller selection
0C2
Earth fault
Grounded motor phase
Check motor/motor cable
Excessive capacitive charging
current of the motor cable
Use shorter motor cables with lower
charging current
0C6
Motor overload (I
2
t overload)
Motor is thermally overloaded, due to:
• impermissable continuous current
• frequent or too long acceleration
processes
• Check controller selection
• Check setting of c20
0H
Controller overtemperature
Controller too hot inside
• Reduce controller load
• Improve cooling
OU
Overvoltage on DC bus
Mains voltage too high
Check mains voltage
Excessively short deceleration time or
motor in generator mode
Increase deceleration time or use
dynamic braking option
Earth leakage on the motor side
Check motor/motor cable
(separate motor from controller)
rF
Flying restart fault
Controller was unable to synchronize
with motor during restart attempt
Check motor/load
rSt
Faulty auto-TRIP reset
More than 8 errors in 10 minutes
Depends on the error
Sd5
Loss of 4-20 mA reference
4-20 mA signal (terminal 8I) is below 2
mA (C34 = 5)
Check signal/signal wire
SF
Single phase fault
A mains phase has been lost
Check mains voltage
(1) The drive can only be restarted if the error message has been reset; see c70
NOTE
In the event of an “OC6” (Motor Overload) failure there is a 3-minute delay before resetting is possible.
This is a requirement of UL508C. This delay is intended to allow time for the motor to cool.
If power is removed when the drive is in an “OC6” fault state, when the power is restored the “OC6” fault
will still be present and the delay will still be active even if power was removed for longer than 3 minutes.
22
Lenze 13466187 EDBTL03 v8
EN, DE, FR, IT, ES