Technical data
General data and operating conditions
l
77
EDK82MV752 DE/EN/FR 7.1
Ambient conditions
Climatic conditions
Storage
IEC/EN 60721−3−1
1K3 (−25 ... +60 °C)
Transport
IEC/EN 60721−3−2
2K3 (−25 ... +70 °C)
Operation
IEC/EN 60721−3−3
3K3 (−20 ... +60 °C)
At temperatures > +40 °C, reduce the rated output current by
2.5 %/°C.
Site altitude
< 4000 m amsl
Reduce rated output current by 5 %/ 1000 m above 1000 m
amsl.
Electrical
Mains connection AC system
Max. mains voltage range
E82MV251... and E82MV371...
1/N/PE or 2/PE 180 V − 0 % ... 264 V + 0 %
E82MV551... to E82MV222...
3/PE 320 V − 0 % ... 550 V + 0 %
E82MV302... to E82MV752...
3/PE 320 V − 0 % ... 550 V + 0 %
Mains frequency
45 Hz − 0 % ... 65 Hz + 0 %
Mechanical
Vibration resistance
(9.81 m/s
2
= 1 g)
Germanischer Lloyd
l
General
conditions
acceleration resistant up to 2 g
Mounting conditions
Mounting position
All mounting positions and mounting alignments are permitted
Free spacess
Above:
To the sides:
100 mm
100 mm
Free spaces with fan
module E82ZMV
for fan exchange:
250 mm
Note regarding the operation with fan module E82ZMV:
The fan module must always be used in the case of
l
motec wall mounting
l
operation without current derating with self−ventilated Lenze motors or Lenze
geared motors
l
operation with non−Lenze motors
Dimensions,
^ Chapter "Mechanical installation"
Weights
^ Chapter "Technical data", "Operation with rated power" or "Operation with
increased rated power"