Commissioning, Important controller codes – Lenze E82MVxxx_4Bxxx User Manual
Page 109

Commissioning
Important controller codes
l
109
EDK82MV752 DE/EN/FR 7.1
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0003*
v
Saving
parameters
non−volatilely
1
0
Do not save parameters in the EEPROM
Data loss after mains switch−off
1
Always save parameters in the EEPROM
l
Active after every mains
connection
l
Cyclic alteration of parameters via
bus module is not permissible
3
Save your own basic setting in the EEPROM Afterwards save parameter set 1 as
own basic setting with C0002 = 9
C0007
v
uSEr
Fixed
configuration
digital inputs
Change of C0007 is copied into the
corresponding subcode of C0410.
Free configuration in C0410 sets
C0007 = 255!
0
E4
E3
E2
E1
l
CW/CCW = clockwise
rotation/counter−clockwise
rotation
l
DCB = DC injection brake
l
QSP = quickstop
l
PAR = change over parameter set
(PAR1
ó PAR2)
– PAR1 = LOW, PAR2 = HIGH
– The terminal in PAR1 and PAR2
has to be assigned with the
"PAR" function.
– Only use configurations with
"PAR" if C0988 = 0
l
TRIP−Set = external error
0
CW/CCW
DCB
JOG2/3
JOG1/3
1
CW/CCW
PAR
JOG2/3
JOG1/3
2
CW/CCW
QSP
JOG2/3
JOG1/3
3
CW/CCW
PAR
DCB
JOG1/3
4
CW/CCW
QSP
PAR
JOG1/3
5
CW/CCW
DCB
TRIP−Set
JOG1/3
6
CW/CCW
PAR
TRIP−Set
JOG1/3
7
CW/CCW
PAR
DCB
TRIP−Set
8
CW/CCW
QSP
PAR
TRIP−Set
9
CW/CCW
QSP
TRIP−Set
JOG1/3
10
CW/CCW
TRIP−Set
UP
DOWN
C0007
v
uSEr
(Continua
tion)
E4
E3
E2
E1
l
Selection of fixed
setpoints
JOG1/3
JOG2/3
LOW LOW
HIGH LOW
LOW HIGH
HIGH HIGH
Active
C0046
JOG1
JOG2
JOG3
11
CW/CCW
DCB
UP
DOWN
12
CW/CCW
PAR
UP
DOWN
13
CW/CCW
QSP
UP
DOWN
14
CCW/QSP
CW/QSP
DCB
JOG1/3
15
CCW/QSP
CW/QSP
PAR
JOG1/3
16
CCW/QSP
CW/QSP
JOG2/3
JOG1/3
17
CCW/QSP
CW/QSP
PAR
DCB
18
CCW/QSP
CW/QSP
PAR
TRIP−Set
19
CCW/QSP
CW/QSP
DCB
TRIP−Set
C0007
v
uSEr
(Continua
tion)
E4
E3
E2
E1
l
UP/DOWN = motor potentiometer
functions
l
H/Re = manual/remote
change−over
l
PCTRL1−I−OFF = switch off I
component of process controller
l
DFIN1−ON = digital frequency
input 0 ... 10 kHz
l
PCTRL1−OFF = switch off process
controller
20
CCW/QSP
CW/QSP
TRIP−Set
JOG1/3
21
CCW/QSP
CW/QSP
UP
DOWN
22
CCW/QSP
CW/QSP
UP
JOG1/3
23
H/Re
CW/CCW
UP
DOWN
24
H/Re
PAR
UP
DOWN
25
H/Re
DCB
UP
DOWN
26
H/Re
JOG1/3
UP
DOWN
27
H/Re
TRIP−Set
UP
DOWN
28
JOG2/3
JOG1/3
PCTRL1−I−OF
F
DFIN1−ON
29
JOG2/3
DCB
PCTRL1−I−OF
F
DFIN1−ON
30
JOG2/3
QSP
PCTRL1−I−OF
F
DFIN1−ON