beautypg.com

Commissioning – Lenze E82MVxxx_4Bxxx User Manual

Page 105

background image

Commissioning

Vector control

6

l

105

EDK82MV752 DE/EN/FR 7.1

Optimising the vector control

In general, the vector control is ready for operation without any further measures after the
motor parameters have been identified. The vector control must only be optimised in the
case of the following drive behaviour:

Drive behaviour

Remedy

Rough motor run and motor current (C0054) > 60 %
rated motor current in idle running (steady−state
operation)

1. Reduce motor stator inductance (C0092) by 10 %
2. Check motor current in C0054
3. If the motor current (C0054) is > 50 % of the rated

motor current:
– Reduce C0092 until the motor current is

approx. 50 % of the rated motor current

– Reduce C0092 by max. 20 %!
– Note: If you reduce C0092, the torque will

decrease!

Torque too low for frequencies f < 5 Hz (starting
torque)

Increase motor resistance (C0084) or motor inductance
(C0092)

Poor speed stability at high load (setpoint and motor
speed are no longer proportional)

Increase slip compensation (C0021)
Overcompensation results in drive instability!

Error messages OC1, OC3, OC4 or OC5 at acceleration
times (C0012) < 1 s (controller is no longer able to
follow the dynamic processes)

Change reset time of the I

max

controller (C0078):

l

Reduce C0078 = I

max

controller becomes faster

(more dynamic)

l

Increase C0078 = I

max

controller becomes slower

("smoother")