Commissioning, Code table – Lenze EDK71MMXXX−020 User Manual
Page 114
7
Commissioning
Code table
EDK71MMXXX−020 DE/EN/FR 5.0
L
114
Code
IMPORTANT
Setting options
No.
Selection
Lenze
Designation
C0002
s
uSEr
(Cont.)
Transfer
parameter sets
with keypad
Keypad
ð
PAR3 (+ FPAR1)
Overwrite the selected
parameter set and FPAR1, if
necessary, with the
corresponding data of the
keypad
73
with function module INTERBUS,
PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
13
with all other function modules
Keypad
ð
PAR4 (+ FPAR1)
74
with function module INTERBUS,
PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
14
with all other function modules
Drive controller
ð
keypad
Copy all available
parameter sets
(PAR1 ... PAR4, if necessary
FPAR1) into the keypad
80
with function module INTERBUS,
PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
20
with all other function modules
Keypad
ð
function module
Overwrite only the
module−specific parameter
set FPAR1 with the
corresponding data of the
keypad
40
with function module INTERBUS,
PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
Function module
ð
keypad
Copy only the
module−specific parameter
set FPAR1 into the keypad
50
with function module INTERBUS,
PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
C0002
s
uSEr
(Cont.)
Save separate
basic setting
9
PAR1
ð
separate basic setting
You can save a separate
basic setting for the
parameters of the drive
controller (e.g. the delivery
state of your machine):
1. Ensure that parameter
set 1 is active
2. Inhibit the controller
3. Set C0003 = 3, confirm
with
v
4. Set C0002 = 9, confirm
with
v
, the separate
basic setting is stored
5. Set C0003 = 1, confirm
with
v
6. Release the controller
Load/copy
separate basic
setting
5
Separate basic setting
ð
PAR1
Restore separate basic
setting in the selected
parameter set
6
Separate basic setting
ð
PAR2
7
Separate basic setting
ð
PAR3
8
Separate basic setting
ð
PAR4