Commissioning, With hand terminal – Lenze EDK71MMXXX−020 User Manual
Page 106

7
Commissioning
With hand terminal
EDK71MMXXX−020 DE/EN/FR 5.0
L
106
The
user menu − The 10 most important drive parameters at a glance
After every mains connection with connected hand terminal or connecting the hand terminal during
operation to the AIF interface, the 10 codes specified in the
user menu (Code C0517) are immediately
available.
The
user menu is set to all codes at the factory to allow for commissioning a standard application:
Code
Designation
Lenze setting
C0054 Apparent motor current of
motor 1
Display only
C0055 Apparent motor current of
motor 2
Display only
C0006 Transfer HW/hand terminal
0
Setting the acceleration time (C0012) and starting voltage
(C0016) via potentiometer, setting the rated motor current
(C0120) via stepping switch
C0120 Rated current
Rated motor current for I
2
t monitoring
1 Motor 1
Accepts the value from the stepping switch:
l
If C0006 = 0, 2, 4, 6:
– Display only
l
If C0006 = 1, 3, 5, 7:
– Rated current can be set via C0120
2 Motor 2
C0410 Configuration of digital input
signals
1 Motor 1 start/stop
1
X3/E1
2 Motor 2 start/stop
2
X3/E2
3 Brake control
3
X3/E3
4 ... 24
255
Not assigned
C0415 Configuration of digital
output signals
1 X3/A1
3
Status of motor 1
2 X3/A2
4
Status of motor 2
3 X3/A3
5
Status of brake
4 X3/A4
25
TRIP error message
5 ... 6 AS−I output bit
255
Not assigned
C0012 Motor voltage acceleration
time
Time for voltage change U
0
... U
mains
1 Motor 1
Accepts the value from potentiometer "T"
l
If C0006 = 0, 1, 2, 3:
– Display only
l
If C0006 = 4, 5, 6, 7:
– Acceleration time can be set via C0012
2 Motor 2
C0423 Delay time of "Release
brake"
0.00 s
C0424 Delay time of "Apply brake"
0.00 s
C0002 Parameter set management
See code table