beautypg.com

4 commissioning – Lenze SCF frequency inverter User Manual

Page 50

background image

50

Lenze 13466146 EDBSF01 v24 EN

4 Commissioning

P55

0-10 VDC ANALOG INPUT

This displays the level of the 0-10 VDC analog input signal at TB-5. A reading of 100% indicates a 10
VDC input at TB-5.

P56

4-20 mA ANALOG INPUT

This displays the level of the 4-20 mA analog input signal at TB-25. A reading of 20% indicates a 4
mA input at TB-25, and a reading of 100% indicates a 20 mA input at TB-25.

P57

TERMINAL STRIP STATUS

This indicates the status of several terminals using the vertical segments of the LED display. An
illuminated segment indicates that the particular terminal is closed with respect to TB-2. The CHARGE
RELAY is not a terminal, and should always be illuminated. Refer to the diagram below:

CHARGE
RELAY

TB-1

TB-12

TB-13A

TB-13B

TB-15

TB-14

TB-13C

P58

KEYPAD AND PROTECTION STATUS

This indicates the status of the buttons on the keypad, and the status of the protective circuitry
in the drive, using the horizontal segments of the LED. An illuminated segment indicates that the
corresponding button is pressed, or the protective circuit is active. Refer to the diagram below:

FCLIM

Mode

OUTPUT

FAULT

p

q

FCLIM is an abbreviation for Fast Current Limit

P59-P60 TB-30 and TB-31 ANALOG OUTPUT

This displays the level of the analog output signals at TB-30 (Parameter 59) and TB-31 (Parameter
60). A reading of 100% indicates that the output is 10 VDC.

This manual is related to the following products: