4 Commissioning
P55
0-10 VDC ANALOG INPUT
This displays the level of the 0-10 VDC analog input signal at TB-5. A reading of 100% indicates a 10
VDC input at TB-5.
P56
4-20 mA ANALOG INPUT
This displays the level of the 4-20 mA analog input signal at TB-25. A reading of 20% indicates a 4
mA input at TB-25, and a reading of 100% indicates a 20 mA input at TB-25.
P57
TERMINAL STRIP STATUS
This indicates the status of several terminals using the vertical segments of the LED display. An
illuminated segment indicates that the particular terminal is closed with respect to TB-2. The CHARGE
RELAY is not a terminal, and should always be illuminated. Refer to the diagram below:
CHARGE
RELAY
TB-1
TB-12
TB-13A
TB-13B
TB-15
TB-14
TB-13C
P58
KEYPAD AND PROTECTION STATUS
This indicates the status of the buttons on the keypad, and the status of the protective circuitry
in the drive, using the horizontal segments of the LED. An illuminated segment indicates that the
corresponding button is pressed, or the protective circuit is active. Refer to the diagram below:
FCLIM
Mode
OUTPUT
FAULT
p
q
FCLIM is an abbreviation for Fast Current Limit
P59-P60 TB-30 and TB-31 ANALOG OUTPUT
This displays the level of the analog output signals at TB-30 (Parameter 59) and TB-31 (Parameter
60). A reading of 100% indicates that the output is 10 VDC.