3 Installation
3.6.2 Two-Wire Start/Stop Control
Shown below is the wiring diagram for a typical two-wire start/stop control scheme, using one
maintained contact (such as that from a PLC) for RUN and STOP commands.
MAINTAINED
RUN/STOP
CONTACT
1 2 5 6
12
TXA TXB
2
13A 13B 13C
14
15
2
STO
P
C
O
MM
ON
0-10 VDC
IN
PU
T
C
O
MM
ON
FOR
W
AR
D
RE
VER
SE
0-10
VDC or 4-20 mA SELECT
C
O
MM
ON
4-20 mA I
N
PU
T
11
25
31
30
The TB-2 terminals are internally connected to each other
NOTE
• Close TB-1 to TB-2 to RUN, and open TB-1 to TB-2 to STOP
• If reverse direction is also required, ROTATION DIRECTION (Parameter 17) must
be set to FORWARD AND REVERSE (02), and TB-13A (Parameter 10) must be set
to START REVERSE (06). If reverse direction is not required, TB-12 must be wired
directly to TB-2
.
• For 0-10 VDC or 4-20 mA speed control, use one of the following methods:
- Program one of the TB-13 terminals (13A, 13B, or 13C) for 0-10 VDC (02) or 4-20
mA (03). When that TB-13 terminal is closed to TB-2, the drive will respond
to the selected speed reference signal. If that TB-13 terminal is not closed to
TB-2, the drive will respond to the speed control source selected in Parameter
05 - STANDARD SPEED SOURCE. This method must be used if it is necessary to
toggle between two speed sources.
- Program Parameter 05 - STANDARD SPEED SOURCE for 0-10 VDC (03) or 4-20
mA (04). This method is preferable if only one speed source is required, as this
method leaves the TB-13 terminals free to be used for other functions.