1 connection to the dc bus (+ug, -ug), Connection to the dc bus (+ug, −ug), Electrical installation – Lenze ECSCKxxx User Manual
Page 54: Warnings
Electrical installation
Power connections
Connection to the DC bus (+U
G
, −U
G
)
l
54
EDKCSCK002 DE/EN/FR 1.1
4.2.1
Connection to the DC bus (+U
G
, −U
G
)
ƒ
With a total cable length of > 20 m, install an axis module or a capacitor
module directly at the power supply module.
ƒ
Twist ±U
G
cables and keep the cable length as short as possible. Pay
attention to short−circuit−proof installation!
ƒ
Cable length > 30 cm:
–
Shield ±U
G
cables.
Fuses
ƒ
When ECS series supply modules with a mains−side protection are used, the
DC−bus supply does not need to be fused.
ƒ
When Lenze devices of the 82xx and 93xx series are used in DC−bus
connections with a continuous DC current > 40 A, install the following fuses:
Fuse
Holder
Value [A]
Lenze type
Lenze type
50
EFSGR0500ANIN
EFH20007
K
Warnings!
ƒ
Use UL−approved cables, fuses and fuse holders only.
ƒ
UL fuse:
– Voltage 500 ... 600 V
– Tripping characteristic "H", "K5" or "CC"
Cable cross−sections
Cable length
1)
Wire end ferrule
Cable
cross−section
Tightening torque
Stripping
length
Up to 20 m
Without wire end ferrule
6 mm
2
(AWG 10)
1.2 ... 1.5 Nm
(10.6 ... 13.3 lb−in)
5 mm
With wire end ferrule
> 20 m
Without wire end ferrule
10 mm
2
(AWG 8)
With wire end ferrule
l
Use pin−end connectors for
wiring!
1)
Cable length from module to module