8 diagnostics, Led status displays, Diagnostics – Lenze E82ZBL-C User Manual
Page 81
Diagnostics
LED status displays
8
EDKMF2102 DE/EN/FR 7.1
81
l
H1_Diagnose−−−(DUMMYSEITEVOR)−−−
8
Diagnostics
LED status displays
Pos.
Colour
Status
Description
0
Green
On
The communication module is supplied with voltage and has a
connection to the drive controller.
Off
The communication module is not supplied with voltage. The
controller or the external voltage supply is switched off.
Blinking
The communication module is supplied with voltage, but is not (yet)
connected to the controller because ...
l
the communication module has not been correctly attached to the
controller;
l
data transfer to/from the controller is not yet possible (e.g.
controller is in initialisation mode).
1
Yellow
Blinking
The controller receives a telegram.
2
Yellow
Blinking
The controller sends a telegram.
3
Red /
green
On /
blinking
The red and green drive LEDs indicate the operating status of the
82XX, 8200 vector, 93XX, 9300 Servo PLC and Drive PLC standard
device (see operating instructions for the standard device).