beautypg.com

Voltage supply – Lenze E82ZBL-C User Manual

Page 62

background image

6

Electrical installation

Voltage supply

EDKMF2102 DE/EN/FR 7.1

62

l

H2_SpgVersorgg−spg

Voltage supply

External voltage supply

)

Note!

Always use a separate power supply unit in every control cabinet and safely
separate it according to EN 61800−5−1 ("SELV"/"PELV") in the case of external
voltage supply and larger distances between the control cabinets.

External voltage supply of the communication module is required if communication is to be
maintained even if the supply of the standard device fails.

If required, feed the communication module with a separate supply voltage via the
two−pole plug connector.

Designation

Description

+

External voltage supply
U = 24 V DC ± 10 %

Reference potential for external voltage supply

This manual is related to the following products: