beautypg.com

3 external voltage supply, External voltage supply, Installation – Lenze E84DGFCG User Manual

Page 24

background image

Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013

24

Installation

Electrical installation

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.2.3

External voltage supply

• The external voltage supply can be used to establish EtherNet/IP communication for

commissioning and to query the data of the digital and analog inputs.

• Furthermore, the external voltage supply serves to maintain EtherNet/IP communication if the

main supply fails.

• The digital inputs RFR, DI1 ... DI5 and the analog input can continue to be evaluated.
• The external voltage supply is done via the terminals 24E and GND of the terminal strip X3.
• Permissible voltage (DC) / max. current:

• U = 24 V DC (20 V - 0 % ... 29 V + 0 %)
• I

max

= 400 mA

• Access to parameters of a device that is disconnected from the mains is not possible.

Hardware manual for Inverter Drives 8400 motec
Here you can find detailed information on how to wire the Communication Unit.