4 write "drivemode" attribute, Implemented cip™ objects – Lenze E84DGFCG User Manual
Page 138

Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013
138
Implemented CIP™ objects
"AC Drive Profile" objects
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Supported service codes
14.3.4
Write "DriveMode" attribute
In order to be able to use the torque control for the assembly object instances 22 (0x16), 23 (0x17),
72 (0x48), 73 (0x49), the "DriveMode" attribute has to be written by means of explicit message
transfer.
In order to write the "DriveMode" attribute by means of explicit message transmission, the
following settings are required:
Service code
[hex]
Name
Description
0x01
Get_Attributes_All
Outputs a list of the attributes and the attribute's values for
a certain object.
0x0E
Get_Attribute_Single
Outputs the value of a certain attribute.
0x10
Set_Attribute_Single
Changes the value of a certain attribute.
Settings
Value / description
Message Type
"CIP Generic"
Service Type
"Set Attribute Single" (service code "0x10")
Class
"2A" (AC Drive Object)
Instance
"1"
Attribute
"6" ("DriveMode" attribute )
Source Element
"Drive_Mode" (variable in the PLC program used as data source for writing.)
Source Length
"1 byte" (The variable data type is SINT.)