3 design of the cables, 4 how to connect the shield, Wiring the installation backplane – Lenze E94AZPP User Manual
Page 53
Wiring the installation backplane
Wiring
Design of the cables
l
53
EDK94ZPP0364 DE/EN/FR/ES/IT 2.1
5.3.3
Design of the cables
ƒ
The cables used must comply with the approvals required for the location
(e.g. UL).
ƒ
It is imperative to comply with the regulations concerning minimum
cross−sections of PE conductors. The cross−section of the PE conductor
must be at least as large as the cross−section of the power connections.
ƒ
The effectiveness of a shielded cable is reached by:
–
Providing a good shield connection through large−surface shield
contact.
–
Using only braided shields with low shield resistance made of tin−plated
or nickel−plated copper braid.
–
Using braided shields with an overlap rate > 70 % and an overlap angle
of 90 °.
–
Keeping unshielded cable ends as short as possible.
Use system cables or shielded cables for these connections:
ƒ
External brake resistor (
, Mounting Instructions of the brake resistor)
The following connections need not be shielded:
ƒ
Mains
ƒ
DC bus
5.3.4
How to connect the shield
E94AZPS004
Fig. 5−5
Connect the shield to the shield sheet (graphics on the right: motor cable for device sizes
II and III)