Profibus watchdog: Monitoring time elapsed [0x01bc8130]
Profibus: Data_Exchange state exited [0x01bc8131]
Profibus watchdog: DP-V1 MSC2 monitoring time exceeded [0x01bc8132]
Response (Lenze setting printed in bold)
Setting:
(; Adjustable response)
:
None System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked Warning ; Information
Cause
Remedy
Permanent interruption of communication to the
PROFIBUS master.
Check cables and terminals.
Response (Lenze setting printed in bold)
Setting:
(; Adjustable response)
:
None System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked Warning ; Information
Cause
Remedy
Data exchange via PROFIBUS has been stopped.
Check cables and terminals.
The slave must receive new parameterisation and
configuration files from the master in order to be able to
exchange data again.
Response (Lenze setting printed in bold)
Setting:
(; Adjustable response)
:
None System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked Warning ; Information
Cause
Remedy
Permanent interruption of communication to C2-
PROFIBUS master.
Check cables and terminals.