beautypg.com

11 diagnostics – Lenze E84AYCPM User Manual

Page 90

background image

Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17

90

11

Diagnostics

11.3

Advanced diagnostic message

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Example: "Short circuit (OC1)" error in the Inverter Drive 8400

Byte

Value

[hex]

Description

1

x Standard data (PRM_Fault)

...

6
7

0A Block length of the advanced diagnostics = 10 bytes

8

81 Status message

9

00 Slot 0

10

01 Status coming

11

00

12

00

13

0B Error message 0x11C4000B "Short circuit (OC1)"

• Error type: "Warning locked"

• Subject area: 0x11C4 (current)

• Error ID: 0x000B

The error number "0x11C4000B" indicates the following:

In the "Current" subject area, an overcurrent has been detected. The error response

to this is a "Warning locked", which must be unlocked separately after the error has

been eliminated.

14

00

15

C4

16

11