beautypg.com

10 monitoring – Lenze E84AYCPM User Manual

Page 82

background image

Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17

82

10

Monitoring

10.2

Short-time interruption of PROFIBUS communication

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

10.2

Short-time interruption of PROFIBUS communication

[10-1] DP states (Decentralized Peripherals) for short-time interruption of communication

The master detects the communication fault and, only after a few microseconds, transfers the slave

to the "WAIT_PRM" status of the DP state machine (see fig.

[10-1]

).

Only after the state chain of the DP state machine ending in the "Data_Exchange" state

(DATA_EXCH) has been passed through, the watchdog monitoring time calculated for the slave (in

milliseconds) continues to run.

Additional monitoring for the data exchange
For this reason an additional monitoring function for the data exchange is available with

C13881

,

which is activated when "Data_Exchange" is exited and the parameterised time (0 ... 65535 ms) has

expired. The active monitoring triggers the response parameterised in

C13880/1

.

2133PFB006

POWER ON

WAIT_PRM

WAIT_CFG

DATA_EXCH

Slave_Diag
Get_Cfg

Set_Slave_Add

Slave_Diag

Chk_Cfg, not o.k.
Set_Prm, not o.k.

Chk_Cfg, o.k.

Slave_Diag
Set_Prm
Get_Cfg

Note!

The watchdog monitoring time does not continue running if the slave does not reach the

"Data_Exchange" state due to repeated communication errors (e.g. caused by loose

contact).

Note!

Observe the following condition for the time setting:
Monitoring time for the data exchange (

C13881

)

watchdog monitoring time of the

PROFIBUS (

C13882/1

).