11 diagnostics – Lenze E84AYCEO User Manual
Page 92

11
Diagnostics
11.1
LED status displays
92
Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
LED
Colour / status
Description
MS
Green
Red
Off
Off
CIP module status: "Nonexistent"
The communication module is not being supplied with voltage.
Off
On
CIP module status: "Major Unrecoverable Fault"
The communication module has a fault that cannot be rectified.
The status is set if the pending status determining device error shows
the "System fault" response.
Off
Blinking
CIP module status: "Major Recoverable Fault"
The communication module has a fault that can be rectified.
The status is set if the pending status determining device error shows
the "Fault", "Trouble", "Quick stop by trouble", "Warning locked", or
"Warning" response.
On
Off
CIP module status: "Operational"
The communication module is working perfectly.
Blinking
Off
CIP module status: "Standby"
The communication module has not been completely configured or the
configuration is defective.
Blinking
Blinking
CIP module status: "Device Self Testing"
The communication module is currently undergoing a self-test.
250 ms
250 ms
250 ms
250 ms
250 ms
250 ms