Ethernet/ip: idle mode [0x01bc8132, Ethernet/ip: duplicate ip address [0x01bc8273, 0x01bc8132 – Lenze E84AYCEO User Manual
Page 100: 0x01bc8273, 12 error messages

12
Error messages
12.2
Possible causes and remedies
100
Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
EtherNet/IP: Idle Mode [0x01bc8132]
EtherNet/IP: Duplicate IP Address [0x01bc8273]
Response (Lenze setting printed in bold)
Setting:
None system fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
• Scanner has received an idle event.
• The scanner is in the "PROG" mode.
• In the "Scanner Command Register", the run/
idle flag (bit 0) is 0.
Set the scanner to the run mode.
Run/idle flag (bit 0) = 1
Response (Lenze setting printed in bold)
Setting: not possible
None system fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
An IP address has been allocated twice within the
network. The addresses of the network nodes must differ
from each other.
Correct the IP address (