Troubleshooting and fault elimination
Status
Cause
Remedy
e.g.
50.0
Present output frequency
Trouble free operation
OFF
Stop
(outputs U, V, W inhibited)
LOW signal at terminal 28
Set terminal 28 to HIGH
1nh
Inhibit
(outputs U, V, W inhibited)
Controller is set up for CANopen
operation (see C01)
Start the controller via CANopen
stP
Output frequency = 0 Hz
(outputs U, V, W inhibited)
Setpoint = 0 Hz (C31 = 0)
Setpoint selection
Quick stop activated through digital
input
Deactivate Quick stop
br
DC-injection brake active
DC-injection brake activated
• via digital input
• automatically
Deactivate DC-injection brake
• digital input = LOW
• automatically after holding time
c06 has expired
CL
Current limit reached
Controllable overload
Automatically (see C22)
LU
Undervoltage on DC bus
Mains voltage too low
Check mains voltage
dEC
Overvoltage on DC bus during
deceleration (warning)
Excessively short deceleration time
(C13)
Automatically if overvoltage
< 1 s,
OU
, if overvoltage > 1 s
nEd
No access to code
Can only be changed when the
controller is in
OFF
or
1nh
Set terminal 28 to LOW or inhibit
through CANopen
Error
Cause
Remedy
(1)
cF
Data on EPM not valid
Data not valid for controller
• Use EPM providing valid data
• Load Lenze setting
CF
Data error
GF
OEM data not valid
F1
EPM error
EPM missing or defective
Power down and replace EPM
CFG
Digital inputs not
uniquely assigned
E1...E3 assigned with the same
digital signals
Each digital signal can only be
used once
Either just “UP” or “DOWN” used
Assign the missing digital signal to
a second terminal
dF
Dynamic braking fault
Dynamic braking resistors are
overheating
Increase deceleration time (C13)
EEr
External error
Digital input “TRIP set” is active
Remove external error
F2...F0,
JF
Internal fault
Please contact Lenze
FC3
CAN communication timeout
Monitored CAN messages not
received
• Check h48 for cause
• Increase timeout settings
• Check CAN wiring
FC5
CAN initialization failed
CAN controller failure
• Perform CAN reset (h58)
• Cycle power
LC
Automatic start inhibited
c42 = 0
LOW-HIGH signal change at
terminal 28
5
Troubleshooting and Fault Elimination
(1) The drive can only be restarted if the error message has been reset; see c70